DL-CT21C2.0 Current Transformer
Flame retardant properties:UL94-V0
Insulation resistance:Normal than 1000MΩ
Work voltage:0.66/0.72kV
Compressive strength:3kV/50Hz/1min
Work frequency:50/60Hz
Operating temperature:-40℃~+85℃
Used for:Load current detection,Electric energy measurement,Microcomputer protection
Installation method:PCB in-line
Dimension ( in mm):
Front view Bottom view Electrical diagram
Technical Data:
|
DL-CT21C2.0 |
Unit |
Rated input |
5 |
A(AC) |
Rated output |
2.5 |
mA(AC) |
Rated sampling load |
100 |
Ω |
Rated sampling voltage |
1.25 |
V(AC) |
Turns ratio |
2000/1 |
—— |
Rated Phase shift |
≤10(RL=0Ω) |
' |
Accuracy |
0.2 |
Level |
Linearity |
0.1 |
% |
Measuring current |
0~5(RL≤1.5KΩ) |
A(AC) |
Maximum current |
0~60(RL≤10Ω) |
A(AC) |
DCR |
210±15 |
Ω |
Weight |
13.7 |
g |
Note:Current transformers are prohibited to be used in open circuit,also can't be connected to fuse。Please connect the output of the transformer first,and then clamp the transformer on the bus under test。