HotLine

025-57220545
网站导航
Split Core Current Transformer
当前位置:主页 > Products > Split Core Current Transformer >

Split core current transformer OPCT10AL

Description:

Flame retardant properties:UL94-V0 Insulation resistance:Normal than 1000MΩ Work voltage:0.66/0.72KV Compressive strength:2KV/50Hz/1min...

Details

OPCT10AL  Split Core Current Transformer

Flame retardant propertiesUL94-V0

Insulation resistanceNormal than 1000MΩ 

Work voltage0.66/0.72KV

Compressive strength2KV/50Hz/1min

Work frequency50Hz~200KHz

Operating temperature-40℃~+85℃

Used forPower project renovation,Power monitoring, Load current detection

Installation methodBusbar perforation,secondary lead output,fixed with cable ties on both sides

Dimensionin/mm:

 

Opening diagram         Front view               Side view        Electrical diagram

Technical Data  

 

OPCT10AL

1000/1

OPCT10AL

2000/1

OPCT10AL

3000/1

Unit

Rated input

5

5

80

AAC

Rated output

5

2.5

26.66

mAAC

Rated sampling load

50

200

100

Rated sampling voltage

0.25

0.5

2.666

VAC

Turns ratio

1000/1

2000/1

3000/1

——

Phase shift

100

5A0Ω

100

5A0Ω

60

80A0Ω

°

Accracy error

0.5

0.5

0.5

%

Linearity

0.3

0.3

0.3

%

Measuring current

0~60A

RL≤10Ω

0~60A

RL≤75Ω

0~80A

RL≤100Ω

AAC

Maximum current

——

0~80A

RL≤10Ω

0~100A

RL≤10Ω

AAC

DCR

50±5

220±20

420±30

Weight

54.2

58.5

50

g

Output line length

1500

2000

1000

mm

Note : Current transformers are prohibited to be used in open circuit,also can’t be connected to fuse.

Please connect the output of the transformer first,and then clamp the transformer on the bus under test.

 


Goods

Nanjing UP Electronic Technology Co.,Ltd  

Address:No.12, qinhuai north road, lishui district, nanjing city, jiangsu province Telephone:025-57220545 E-mail:wang0701j@163.com